COMPOSITE SUPPORT INSULATOR Maira W 12,5.05.174

ENVIRONMENT CONDITIONS
Maximum ambient temperature + 50 °C
Minimum ambient temperature – 55 °C
Maximum humidity 100 %
Altitude above sea level 2500 m
Radiation of sun Strong
Position of installation Outdoor/Indoor

                        
TECHNICAL DATA
Standard to be applied IEC 61952
Nominal system voltage 12,5 KV
Highest voltage of system  15 KV
Nominal system frequency  50/60 Hz
Withstanding voltage with frequency power during 1 minute in dry condition
(to earth & between phases)
70 KV
Withstanding voltage with frequency power during 1 minute in wet condition  45 KV
Lightning impulse flashover voltage (positive) –50%  95 KV
Lightning impulse flashover voltage (negative) –50% 110 KV
Thickness of galvanization of metal part - SR EN 10083/1 70 μm Zn
Fittings – IEC 61466–2/2002  Clamp
Kind of material Silicone rubber ( HTV)
Specified mechanical load 1125 lbs
Creepage distance – IEC 815 /1986 15.27 inch
Exceptional maximum tensile strenght 1282.5 lbs
Length - SR EN 60383/1 6.6 inch
Weight 2.22 kg
Polluted level – IEC 815/1986  IV (3,1 cm/KV)