COMPOSITE SUPPORT INSULATOR Maira R 3,6.05.114

ENVIRONMENT CONDITIONS
Maximum ambient temperature + 50 °C
Minimum ambient temperature – 55 °C
Maximum humidity 100 %
Altitude above sea level 2500 m
Radiation of sun Strong
Position of installation Outdoor/Indoor

                        
TECHNICAL DATA
Standard to be applied IEC 61952
Nominal system voltage 3.6 KV
Highest voltage of system  6 KV
Nominal system frequency  50/60 Hz
Withstanding voltage with frequency power during 1 minute in dry condition
(to earth & between phases)
30 KV
Withstanding voltage with frequency power during 1 minute in wet condition  20 KV
Lightning impulse flashover voltage (positive) –50%  40 KV
Lightning impulse flashover voltage (negative) –50% 45 KV
Thickness of galvanization of metal part - SR EN 10083/1 70 μm Zn
Fittings – IEC 61466–2/2002 Cylindrical M10 / M16
Kind of material Silicone rubber ( HTV)
Specified mechanical load 1125 lbs
Creepage distance – IEC 815 /1986 7.38 inch
Exceptional maximum tensile strenght 1282.5 lbs
Length - SR EN 60383/1 5.55 inch
Weight 1.33 LBS
Polluted level – IEC 815/1986  II (2,1 cm/KV)