COMPOSITE SUPPORT INSULATOR Maira R 3,6.05.114
ENVIRONMENT CONDITIONS | ||
Maximum ambient temperature | + 50 °C | |
Minimum ambient temperature | – 55 °C | |
Maximum humidity | 100 % | |
Altitude above sea level | 2500 m | |
Radiation of sun | Strong | |
Position of installation | Outdoor/Indoor | |
|
||
TECHNICAL DATA | ||
Standard to be applied | IEC 61952 | |
Nominal system voltage | 3.6 KV | |
Highest voltage of system | 6 KV | |
Nominal system frequency | 50/60 Hz | |
Withstanding voltage with frequency power during 1 minute in dry condition
(to earth & between phases) |
30 KV | |
Withstanding voltage with frequency power during 1 minute in wet condition | 20 KV | |
Lightning impulse flashover voltage (positive) –50% | 40 KV | |
Lightning impulse flashover voltage (negative) –50% | 45 KV | |
Thickness of galvanization of metal part - SR EN 10083/1 | 70 μm Zn | |
Fittings – IEC 61466–2/2002 | Cylindrical M10 / M16 | |
Kind of material | Silicone rubber ( HTV) | |
Specified mechanical load | 1125 lbs | |
Creepage distance – IEC 815 /1986 | 7.38 inch | |
Exceptional maximum tensile strenght | 1282.5 lbs | |
Length - SR EN 60383/1 | 5.55 inch | |
Weight | 1.33 LBS | |
Polluted level – IEC 815/1986 | II (2,1 cm/KV) | |
|