COMPOSITE BUSHING INSULATOR Maira M 24/630.03.500

Composite bushing insulators are used for crossing current bars from indoor to outdoor, while ensuring an adequate level of insulation
ENVIRONMENT CONDITIONS
Maximum ambient temperature + 50 °C
Minimum ambient temperature – 55 °C
Maximum humidity 100 %
Altitude above sea level 2500 m
Dynamic category N – SR HD 478.2.1.S1
Use category 3 – SR 1054-93


TECHNICAL DATA
Nominal system voltage 24 KV
Current rate  630 A
Individual mechanical load (bending)  3 KN
Rated short time withstand current 40 kAmax
Weight  6 kg
Window  Min.300/300; max.400x400 mm
Length 500 mm
Current bar Aliaj de Cu ; S =200 mmp
Sheet dimensions 400x400 mm
Sheet Composite material
Main characteristics of the composite support insulators
Characteristics Composite support insulator outdoor/indoor
Creepage distance 748 mm
Highest voltage of system 24 KV
Lightning impulse withstanding voltage 200 KV
Withstanding voltage with frequency power in wet condition 90 KV
Polluted level IV