COMPOSITE SUPPORT INSULATOR Maira A 7,2.4,5.144

ENVIRONMENT CONDITIONS
Maximum ambient temperature + 50 °C
Minimum ambient temperature – 55 °C
Maximum humidity 100 %
Altitude above sea level 2500 m
Radiation of sun Strong
Position of installation Outdoor/Indoor

                        
TECHNICAL DATA
Standard to be applied IEC 61952
Nominal system voltage 7.2 KV
Highest voltage of system  9 KV
Nominal system frequency  50 Hz
Withstanding voltage with frequency power during 1 minute in dry condition
(to earth & between phases)
50 KV
Withstanding voltage with frequency power during 1 minute in wet condition  30 KV
Lightning impulse flashover voltage (positive) –50%  70 KV
Lightning impulse flashover voltage (negative) –50% 85 KV
Thickness of galvanization of metal part - SR EN 10083/1 70 μm Zn
Fittings – IEC 61466–2/2002 Cylindrical M10 / M16
Kind of material Silicone rubber ( HTV)
Specified mechanical load 1012.5 lbs
Creepage distance – IEC 815 /1986 12.62 inch
Exceptional maximum tensile strenght 1350 lbs
Length - SR EN 60383/1 5.7 inch
Weight 1.66 LBS
Polluted level – IEC 815/1986  II (2,1 cm/KV)